Operating renewable energy plant

The alarms during operation are divided according to the importance of the warning. By importance, each step has a different guaranteed response time to spare for remediation. The main crash alerts include the following but can be changed according to user needs:
a) Level 1 (Critical Fault - highest priority incident)
- (i) PV system at the plant is fully or partially flooded
- (ii) Transformer flooding
- (iii) Completely disconnected from any junction/combiner boxes
- (iv) Power failure of transformer
- (v) When any medium voltage protective relay mode is activated
- (vi) When the plant is disconnected from the regional electricity network
- (vii) When there is a fire or explosion in the station/factory area
- (viii) Any incident with the same consequences as mentioned above
b) Level 2 (Fault - priority issue)
- (i) Loss of power generation capacity of the inverter
- (ii) Electric meter is faulty
- (iii) The readings from the meteorological station are inconsistent
- (iv) Relatively low inverter capacity compared to similar sized inverters
c) Level 3 (Warning - needs attention for trend analysis)
- (i) Inverter internal temperature seizes up to a warning level
- (ii) String, Combiner box, Inverter PR levels down to unexpected level
- (iii) The temperature inside the inverter reaches the warning level
- (iv) String, Combiner box, Inverter PR have unexpected warnings
- d) Level 4 (Notice - not considered an incident but rather a notification for trend analysis)
- (i) ACB reported an error
- (ii) Inverter error (Run, Stop)
e) Processing time
| Level |
Division |
Type of incident |
Processing time |
Notification |
| Level 1 |
Critical |
x |
Within 2 hours |
Manager |
| Level 2 |
Fault |
x |
Within 24 hours |
Manager |
| Level 3 |
Warning |
- |
Within 72 hours |
Operator |
| Level 4 |
Notice |
- |
- |
Operator |

SCB Checking

Cable checking